Clear spirit

Team, innovation, professionalism, integrity

ZYC series On-load tap-changer filter oil machine

Release time: 2016-11-29   Read:

abstract: Use: It is mainly used in the bypass circulation filtering system of OLTC. It can timely filer oil while the transformer operates normally, or it can automatically filter the oil after switching of the OLTC. The equipment can efficiently discord

Use:

It is mainly used in the bypass circulation filtering system of OLTC. It can timely filer oil while the transformer operates normally, or it can automatically filter the oil after switching of the OLTC. The equipment can efficiently discord the impurities like dissociated carbon, Water and oxides in the filtering cycles to ensure the quality of oil, thus it can guarantee the oil insulation ,increasing the switching times, postponing the repairing ,decreasing the power cut off times, assuring the  voltage  quantity and improving the safety and reliability of the OLTC.

ZYC is usually installed near the OLTC permanently (the hanging installation or fixed installation beside).There are many kinds of flow rate and accessories with different functions choose.

Feature:

1: Stainless steel.

2: Standard control box.

3: Remote control system: filter element display of machine operation.

4: Positive and negative direction control of the motor, protection of over-load of motor start and phase-lacking.

5: Humidity relay, 50%-100%adjustable.

6:Automatically run the filter equipment once after the operation of OLTC ,start up the operation time can be set according to requirement from 0-99 hours ,but it is usually set with 30 minutes .Another way is to filter every day at the fixed time lasting two hours. The two methods can be chosen accordingly.

Technical  parameter  list

project

dataname

Unit / type

ZYC-10

Technical parameter list

Flow

L/min

10

Working pressure

Mpa

≤0.5

Power supply

KW

三相四线(380V-50HZ

Total power

KW

0.75

Inlet(outlet )Diameter

DN

25

Outer size

mm

530×350×1000

weight

Kg

100

After filtration

Impurity size

μm

1

cleanliness

NAS1638

≤6

Top